Upset Conditions and Countermeasures

Excerpt

The first action to be taken in case of exceeding specified chemical limits is to check the sampling system for the following:

• Adequate sample flow

• Correct sample temperature

• Exhausted cation exchanger cartridge

• Out-of-calibration analyzer (oxygen, silica, pH, conductivity, sodium)

Table 5 lists some of the more typical problems, their causes and the necessary countermeasures. Use of blowdown as a corrective action should be a temporary action until the chemistry parameter is brought back into conformance. NOTE: This list is an example only and may be incomplete. Each deviation from a specified value requires careful investigation.